Application
The general purpose vibration point level switch provides reliable liquid level detection of dirty liquids such as those with light to medium coating, scaling or foaming characteristics with a 1A relay output. Media examples include wastewater, diluted caustic soda and light weight oil. For optimum performance, the liquid level switch automatically adjusts for coating build up, and if necessary, outputs a proactive maintenance alarm to request cleaning. The submersible Ryton® liquid level sensor is universally mounted through the tank wall or inside the tank as a high level alarm or low level alarm.
Features
 |
Automatic coating adjustment optimizes sensor performance |
 |
Submersible Ryton® sensor with polypropylene cable for corrosive liquids |
 |
Coating alarm proactively alerts user when cleaning is required |
 |
60VA relay selectable NO or NC via power supply wiring polarity |
Specifications
| Orientation: |
Universal |
| Accuracy: |
± 1mm in water |
| Repeatibility: |
± 0.5mm in water |
| Supply voltage: |
12-28 VDC |
| Consumption: |
25 mA maximum |
| Contact type: |
(1) SPST relay |
| Contact rating: |
60 VA, 1A maximum |
| Contact output: |
Selectable NO / NC |
| Maint. alarm: |
NPN transistor, 10 mA
maximum |
| Process temp.: |
F: -40° to 176°
C: -40° to 80° |
| Pressure: |
150 psi (10 bar) @ 25º
C., derated @ 1.667
psi (0.113 bar) per ºC.
above 25º C. |
| Sensor rating: |
NEMA 6 (IP68) |
| Sensor material: |
Ryton® |
| Grommet mat.: |
Viton® |
| Cable jack. mat.: |
PP |
| Cable type: |
5-conductor, shielded |
| Cable length: |
10' (3m) |
| Process mount: |
3/4" NPT (3/4" G) |
| Mount. gasket: |
Viton® |
| Classification: |
General purpose |
| Compliance: |
CE |